High Integration: Modular design for easy maintenance.
Scalable Deployment: Deployable according to demand; supports parallel connection of multiple cabinets.
Advanced Grid Support: Supports off-grid operation with seamless switching between VF (Voltage-Frequency) and PQ (Active-Reactive Power) modes.
Safety First: Multiple electrical protections, proactive warnings, and proactive protection.
Smart Connectivity: Supports IoT and cloud platforms.
Physical Layout: Bottom wiring design.
| Parameter | Specification |
| Grid Voltage | 400Vac (Three-phase Four-wire) |
| Rated AC Power | 125KW |
| Rated AC Current | 180A |
| Rated Grid Frequency | 50/60Hz |
| Adjustable Power Factor Range | -1 (Leading) to +1 (Lagging) |
| THDi (Rated Power) | < 3% |
| Output Method | Bottom wiring design |
| Parameter | Specification |
| Battery Module | LFP-166.4V-314Ah-52.2496KWh |
| Total Capacity | 261.25KWh |
| Rated Voltage | 832Vdc |
| Operating Voltage Range | 715 ~ 923Vdc |
| Maximum Current | 200A |
| Parameter | Specification |
| Isolation Method | Non-isolated |
| Charge/Discharge Rate | 0.5C |
| System Life | 8000 cycles @25°C, 0.5C, 95% DOD, ≥70% EOL |
| Communication Interface | RS485, CAN, LAN |
| Altitude | ≤3500m (Derating above 2000m) |
| Operating Temperature | -20℃ ~ 50℃ |
| Protection Level | IP55 |
| Weight | 2.2 Tons |
| Dimensions (WDH) | 880 * 1250 * 2200 mm |
| Certifications | GB/T36276, GB/T34131, UL1973, UL9540A, IEC62619, UN38.3 |